Twenty-eight standard transformer ratings from 0.25 to 5,000 kVA, with the full-load current each produces at four common voltages.
Data verified 2026-09-29 · based on IEEE C57.12.00-2021
| Rating kVA[2] | 208 V 3φ A[1] | 480 V 3φ A[1] | 240 V 1φ A[1] | 120 V 1φ A[1] |
|---|---|---|---|---|
| 0.25 # | 0.7 | 0.3 | 1.0 | 2.1 |
| 0.5 # | 1.4 | 0.6 | 2.1 | 4.2 |
| 0.75 # | 2.1 | 0.9 | 3.1 | 6.2 |
| 1 # | 2.8 | 1.2 | 4.2 | 8.3 |
| 1.5 # | 4.2 | 1.8 | 6.2 | 12.5 |
| 2 # | 5.6 | 2.4 | 8.3 | 16.7 |
| 3 # | 8.3 | 3.6 | 12.5 | 25.0 |
| 5 # | 13.9 | 6.0 | 20.8 | 41.7 |
| 7.5 # | 20.8 | 9.0 | 31.2 | 62.5 |
| 10 # | 27.8 | 12.0 | 41.7 | 83.3 |
| 15 # | 41.6 | 18.0 | 62.5 | 125.0 |
| 25 # | 69.4 | 30.1 | 104.2 | 208.3 |
| 37.5 # | 104.1 | 45.1 | 156.2 | 312.5 |
| 50 # | 138.8 | 60.1 | 208.3 | 416.7 |
| 75 # | 208.2 | 90.2 | 312.5 | 625.0 |
| 100 # | 277.6 | 120.3 | 416.7 | 833.3 |
| 150 # | 416.4 | 180.4 | 625.0 | 1250.0 |
| 167 # | 463.5 | 200.9 | 695.8 | 1391.7 |
| 225 # | 624.5 | 270.6 | 937.5 | 1875.0 |
| 300 # | 832.7 | 360.8 | 1250.0 | 2500.0 |
| 500 # | 1387.9 | 601.4 | 2083.3 | 4166.7 |
| 750 # | 2081.8 | 902.1 | 3125.0 | 6250.0 |
| 1000 # | 2775.7 | 1202.8 | 4166.7 | 8333.3 |
| 1500 # | 4163.6 | 1804.2 | 6250.0 | 12500.0 |
| 2000 # | 5551.4 | 2405.6 | 8333.3 | 16666.7 |
| 2500 # | 6939.3 | 3007.0 | 10416.7 | 20833.3 |
| 3750 # | 10409.0 | 4510.5 | 15625.0 | 31250.0 |
| 5000 # | 13878.6 | 6014.1 | 20833.3 | 41666.7 |
Standard ratings follow a preferred-number series, which is why 37.5, 75 and 167 kVA appear alongside 50, 100 and 150 — the intermediate sizes exist so a transformer can be matched to a load without excessive oversizing. Above 500 kVA the steps widen sharply and the rating is often specified rather than selected.
Current falls as voltage rises for the same kVA: a 75 kVA transformer draws 208 A at 208 V three-phase and 90 A at 480 V three-phase. The transformer is the same device; only the winding ratio differs, and that is why the same kVA can serve very different loads depending on the distribution voltage.
These are full-load currents for sizing the transformer's own circuit. The primary protection, secondary conductors and secondary overcurrent device are each sized separately, and the primary device is typically not the same rating as the secondary.
Transformers are sized on the connected load, not on the sum of the nameplate ratings of everything that might run. Three corrections matter.
Diversity — not all loads run at once. A building with 200 kVA of connected load might peak at 120 kVA, and a transformer sized at 200 kVA would be running at 60% of capacity, which is inefficient but also gives room for growth.
Motor starting — a large motor draws several times its full-load current during starting, causing a voltage dip. Transformer impedance, not just rating, determines how deep that dip is, so a marginally sized transformer can cause starting problems even though its continuous rating is adequate.
Harmonics — non-linear loads such as variable-frequency drives and switch-mode supplies cause additional heating that the kVA rating does not capture. Where a significant share of the load is non-linear, the transformer is derated or a K-rated unit is specified.
A transformer loaded to about 50 to 75% of rating usually runs most efficiently and has the least temperature rise for its life. Loading to 100% continuously is permitted but shortens insulation life and leaves no margin for growth.
Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | Value computed from the standard's defining relationship | derived | Computed at build time from the defining formula and checked against every row. |
| [2] | IEEE C57.12.00 — General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers | standard | IEEE C57.12.00-2021 |
| [3] | NEC Article 450 — Transformers and Transformer Vaults | standard | NEC 2023 (NFPA 70-2023) |
| Standard | Revision | What it covers on this page |
|---|---|---|
| IEEE C57.12.00 — General Requirements for Distribution Transformers | IEEE C57.12.00-2021 | the standard kVA rating series |
| NEC Article 450 — Transformers and Transformer Vaults | NEC 2023 (NFPA 70-2023) | protection and conductor sizing for transformer circuits |
| NEC Article 220 — Branch-Circuit, Feeder and Service Load Calculations | NEC 2023 (NFPA 70-2023) | the load calculation basis for sizing |
Cross-checked against:
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| Full-load current at four voltages | Single-phase: I = kVA × 1000 ÷ V. Three-phase: I = kVA × 1000 ÷ (√3 × V). Recomputed at build time for every row. |
Ratings are standard sizes and currents are full-load figures for the transformer's own circuit. Sizing a transformer requires the connected load with diversity, and primary and secondary protection are sized separately under NEC Article 450.
Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.