Engineering Reference

Grounding Conductor Size Chart

Minimum equipment grounding conductor sizes by the rating of the overcurrent device ahead of the equipment, in copper and aluminium.

Data verified 2026-09-29 · based on NEC 2023 (NFPA 70-2023)

Minimum Equipment Grounding Conductor (NEC Table 250.122)

Overcurrent device rating[1]Amperes[1]Copper[1]Aluminium or copper-clad[1]
15 A #151412
20 A #201210
30 A #30108
40 A #40108
60 A #60108
100 A #10086
200 A #20064
300 A #30042
400 A #40031
500 A #50021/0
600 A #60012/0
800 A #8001/03/0
1000 A #10002/04/0
1200 A #12003/0250 kcmil
1600 A #16004/0350 kcmil
2000 A #2000250 kcmil400 kcmil
2500 A #2500350 kcmil600 kcmil
3000 A #3000400 kcmil600 kcmil
4000 A #4000500 kcmil750 kcmil
5000 A #5000700 kcmil1200 kcmil
6000 A #6000800 kcmil1200 kcmil

The equipment grounding conductor is sized from the overcurrent device rating, not from the phase conductors. That is deliberate: its job is to carry fault current long enough for the overcurrent device to open, and that current is set by the device, not by the conductor ampacity.

The consequence is counter-intuitive — the grounding conductor can be much smaller than the phase conductors, and it does not need to be increased just because the phases were upsized for voltage drop.

That last point has a real exception. Where the phase conductors are increased in size to limit voltage drop, the grounding conductor must be increased proportionally. It is an easy requirement to miss, and it is why a long feeder with upsized phases may need a larger equipment ground than the table shows.

Why It Can Be Smaller Than the Phase Conductors

The phase conductors must carry the load current continuously without overheating. The grounding conductor carries current only during a fault, and only for as long as it takes the overcurrent device to open — milliseconds to a few seconds.

Its sizing therefore comes from a different question: can it carry the available fault current for that duration without being destroyed, and is its impedance low enough that the fault current actually trips the device? Both are satisfied by a conductor much smaller than the phases.

The proportional-increase rule exists because that second condition can fail. A long feeder has enough impedance to limit fault current, and if the phases are upsized for voltage drop the ground path may be left relatively too small — so the Code requires the ground to grow with them.

Frequently Asked Questions

How do I size an equipment grounding conductor?
From the rating of the overcurrent device ahead of the equipment, using NEC Table 250.122. A 100 A device needs a #8 copper equipment ground, a 400 A device a #3, and a 2000 A device a 250 kcmil. The phase conductor size is not used for this.
Can the grounding conductor be smaller than the phase conductors?
Usually yes, and often much smaller. It carries current only during a fault, so it is sized to survive the fault and to trip the device rather than to carry load continuously. The exception is when the phase conductors are upsized for voltage drop — then the ground must be increased proportionally.
What is the minimum size grounding conductor?
For a 15 A circuit it is #14 copper, for 20 A it is #12, and for 30 A through 60 A it is #10. It does not go below #14 copper in the table, and a larger circuit cannot be given a smaller ground than its device rating calls for.
Does the grounding conductor have to be in the same raceway?
It must be run with the circuit conductors, in the same raceway, cable or trench. Separating it creates a loop with a different impedance and can cause circulating currents and unpredictable fault paths.
What is the difference between grounding and bonding?
Grounding connects the system to earth; bonding connects conductive parts to each other so they stay at the same potential. The equipment grounding conductor does both jobs — it bonds the equipment enclosure to the system and provides the fault path that trips the breaker.

Related

Value Sources

Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.

#SourceTypeRevision / method
[1]NEC Table 250.122 — Minimum Size Equipment Grounding Conductors for Grounding Raceway and EquipmentstandardNEC 2023 (NFPA 70-2023)

Data Sources

StandardRevisionWhat it covers on this page
NEC Table 250.122 — Minimum Size Equipment Grounding ConductorsNEC 2023 (NFPA 70-2023)every conductor size in the table
NEC Article 250.122(B) — Increased in SizeNEC 2023 (NFPA 70-2023)the proportional-increase rule for upsized phases
NEC Article 250.118 — Types of Equipment Grounding ConductorsNEC 2023 (NFPA 70-2023)what may serve as the grounding conductor

Cross-checked against:

Sizes are the minimum permitted. Where phase conductors are increased for voltage drop, the equipment grounding conductor must be increased proportionally. The requirements for specific equipment — swimming pools, agricultural buildings, separately derived systems — modify the general table.

Accuracy and use. The values on this page are compiled from the published standards and cross-checked sources listed above. Where values are derived, the derivation is stated. No warranty, express or implied, is made as to the accuracy or completeness of this information, and no liability is accepted for any loss or damage arising from its use. Engineering reference data is provided for guidance in preliminary work — before a value is used for design, fabrication or acceptance testing, verify it against the current revision of the governing standard and against your own inspection. The user assumes all risk and responsibility in connection with the use of this information.

Cite This Page

Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:

Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.