Sources and scope for this page: NEC Article 240.6 — Standard Ampere Ratings for Fuses and Inverse Time Circuit Breakers (NEC 2023 (NFPA 70-2023)), covering every rating in the table; and NEC Article 210.20 — Overcurrent Protection for Branch Circuits (NEC 2023 (NFPA 70-2023)), covering the 125% continuous-load requirement (one more source is tabulated below). No independent source check is recorded for this page: the content rests on the sources listed and on the working shown on the page. Full sources, values and limits on this page.
Page last changed 2026-10-19 · based on NEC 2023 (NFPA 70-2023)
Standard Ampere Ratings (NEC 240.6)
| Standard rating[2] | Amperes[2] | Continuous load (80%) A[1] | Load at 125% A[1] | Typical application[2] |
|---|---|---|---|---|
| 15 A # | 15 | 12.0 | 18.8 | Branch circuits — receptacles, lighting, small appliances |
| 20 A # | 20 | 16.0 | 25.0 | Branch circuits — receptacles, lighting, small appliances |
| 25 A # | 25 | 20.0 | 31.2 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 30 A # | 30 | 24.0 | 37.5 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 35 A # | 35 | 28.0 | 43.8 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 40 A # | 40 | 32.0 | 50.0 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 45 A # | 45 | 36.0 | 56.2 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 50 A # | 50 | 40.0 | 62.5 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 60 A # | 60 | 48.0 | 75.0 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 70 A # | 70 | 56.0 | 87.5 | Subpanels and feeder circuits |
| 80 A # | 80 | 64.0 | 100.0 | Subpanels and feeder circuits |
| 90 A # | 90 | 72.0 | 112.5 | Subpanels and feeder circuits |
| 100 A # | 100 | 80.0 | 125.0 | Subpanels and feeder circuits |
| 110 A # | 110 | 88.0 | 137.5 | Service and feeder circuits, small commercial |
| 125 A # | 125 | 100.0 | 156.2 | Service and feeder circuits, small commercial |
| 150 A # | 150 | 120.0 | 187.5 | Service and feeder circuits, small commercial |
| 175 A # | 175 | 140.0 | 218.8 | Service and feeder circuits, small commercial |
| 200 A # | 200 | 160.0 | 250.0 | Service and feeder circuits, small commercial |
| 225 A # | 225 | 180.0 | 281.2 | Service and feeder circuits, small commercial |
| 250 A # | 250 | 200.0 | 312.5 | Commercial services and distribution |
| 300 A # | 300 | 240.0 | 375.0 | Commercial services and distribution |
| 350 A # | 350 | 280.0 | 437.5 | Commercial services and distribution |
| 400 A # | 400 | 320.0 | 500.0 | Commercial services and distribution |
| 450 A # | 450 | 360.0 | 562.5 | Large commercial and light industrial distribution |
| 500 A # | 500 | 400.0 | 625.0 | Large commercial and light industrial distribution |
| 600 A # | 600 | 480.0 | 750.0 | Large commercial and light industrial distribution |
| 700 A # | 700 | 560.0 | 875.0 | Large commercial and light industrial distribution |
| 800 A # | 800 | 640.0 | 1000.0 | Large commercial and light industrial distribution |
| 1000 A # | 1000 | 800.0 | 1250.0 | Industrial switchgear and main distribution |
| 1200 A # | 1200 | 960.0 | 1500.0 | Industrial switchgear and main distribution |
| 1600 A # | 1600 | 1280.0 | 2000.0 | Industrial switchgear and main distribution |
| 2000 A # | 2000 | 1600.0 | 2500.0 | Industrial switchgear and main distribution |
| 2500 A # | 2500 | 2000.0 | 3125.0 | Industrial switchgear and main distribution |
| 3000 A # | 3000 | 2400.0 | 3750.0 | Industrial switchgear and main distribution |
| 4000 A # | 4000 | 3200.0 | 5000.0 | Industrial switchgear and main distribution |
| 5000 A # | 5000 | 4000.0 | 6250.0 | Industrial switchgear and main distribution |
| 6000 A # | 6000 | 4800.0 | 7500.0 | Industrial switchgear and main distribution |
Breakers are manufactured only in the ratings listed — the series is fixed by NEC 240.6, not by what would be convenient. There is no 55 A, 65 A, 75 A or 90 A breaker in the standard series, so a calculated load must be rounded up to the next standard size.
The continuous-load column is 80% of the rating, because a breaker carrying a continuous load (three hours or more) may be loaded only to 80% of its rating unless the assembly is listed for 100%. Equivalently, the breaker must be at least 125% of the continuous load — which is the inverse-time column.
Standard ratings above 1,200 A are normally only available as adjustable-trip moulded case or insulated case breakers, where the rating is set within a range rather than fixed.
Why the Rating Must Be Rounded Up
A branch circuit's overcurrent device must protect the conductor. The conductor's ampacity comes from the ampacity table, adjusted for ambient temperature and the number of conductors in the raceway — and the breaker must not exceed that adjusted ampacity.
The practical sequence is: calculate the load, apply the 125% factor for continuous loads, then select the next standard size up. That last step matters because the calculated figure almost never lands on a standard rating. A 42 A continuous load needs 52.5 A, which rounds to a 60 A breaker — and the conductor must then be sized to carry 60 A, not 52.5 A.
One exception is worth knowing: the next-size-up rule may be applied to the next standard rating only, not the one after. A load that needs 130 A cannot be served by a 150 A breaker on a 125 A conductor — the conductor must be increased instead.
Frequently Asked Questions
- What are the standard circuit breaker sizes?
- 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 amperes, per NEC 240.6.
- Why is there no 55 amp breaker?
- Because the standard series is fixed and does not include it. The gaps widen as the ratings rise: 225 to 250, then 250 to 300, then 300 to 350. A load between two standard sizes must be served by the next size up, with the conductor sized accordingly.
- What is the 80% rule for breakers?
- A breaker may carry a continuous load — one lasting three hours or more — at no more than 80% of its rating. So a 20 A breaker carries 16 A continuously. Equivalently, the breaker must be sized at 125% of the continuous load. Non-continuous loads may use the full rating.
- Can I use a larger breaker than the conductor rating?
- Generally no — the breaker protects the conductor. The exception is motors, where the short-circuit protection may be sized well above the conductor ampacity because the motor's overload relay provides the overload protection. That exception is specific to motor circuits.
- What is an adjustable-trip breaker?
- A breaker whose trip rating can be set within a range, rather than being fixed at manufacture. Above 1,200 A they are the norm, which is why the standard series becomes less meaningful at high ratings — the breaker is set to the calculated value rather than selected from a list.
Related
Value Sources
References and calculation methods used for this page are listed below. Numbered markers connect table columns where present. A reference listing does not itself establish that every value has been independently checked.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | Value computed from the standard's defining relationship | derived | Computed at build time from the defining formula and checked against every row. |
| [2] | NEC Article 240.6 — Standard Ampere Ratings for Fuses and Inverse Time Circuit Breakers | reference | NEC 2023 (NFPA 70-2023) |
Data Sources
| Standard | Revision | What it covers on this page |
|---|---|---|
| NEC Article 240.6 — Standard Ampere Ratings for Fuses and Inverse Time Circuit Breakers | NEC 2023 (NFPA 70-2023) | every rating in the table |
| NEC Article 210.20 — Overcurrent Protection for Branch Circuits | NEC 2023 (NFPA 70-2023) | the 125% continuous-load requirement |
| NEC Article 240.4 — Protection of Conductors | NEC 2023 (NFPA 70-2023) | the next-size-up allowance and its limits |
Verification scope
No page-specific independent source review is recorded here. The listed references and formulas explain the basis of the compilation; automated consistency checks do not verify the original sources or establish product conformity.
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| Continuous-load and 125% columns | 80% and 125% of the standard rating — exact reciprocals of each other. |
Ratings are the standard series only. Selecting a breaker requires the calculated load, the conductor ampacity after adjustment, and the applicable code article. Above 1,200 A most breakers are adjustable-trip and the rating is set rather than selected.
Cite This Page
Read the source notes, calculation methods and verification scope above before reusing a value. To cite this page:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.