Allowable current-carrying capacity for copper conductors by wire size and insulation temperature rating, per NEC Table 310.16.
Page last changed 2026-10-19 · based on NEC 2023 (NFPA 70-2023)
| Size[1] | 60 °C A[1] | 75 °C A[1] | 90 °C A[1] |
|---|---|---|---|
| 14 # | 15 | 20 | 25 |
| 12 # | 20 | 25 | 30 |
| 10 # | 30 | 35 | 40 |
| 8 # | 40 | 50 | 55 |
| 6 # | 55 | 65 | 75 |
| 4 # | 70 | 85 | 95 |
| 3 # | 85 | 100 | 115 |
| 2 # | 95 | 115 | 130 |
| 1 # | 110 | 130 | 145 |
| 1/0 # | 125 | 150 | 170 |
| 2/0 # | 145 | 175 | 195 |
| 3/0 # | 165 | 200 | 225 |
| 4/0 # | 195 | 230 | 260 |
| 250 kcmil # | 215 | 255 | 290 |
| 300 kcmil # | 240 | 285 | 320 |
| 350 kcmil # | 260 | 310 | 350 |
| 400 kcmil # | 280 | 335 | 380 |
| 500 kcmil # | 320 | 380 | 430 |
| 600 kcmil # | 350 | 420 | 475 |
| 700 kcmil # | 385 | 460 | 520 |
| 750 kcmil # | 400 | 475 | 535 |
| 1000 kcmil # | 455 | 545 | 615 |
Values are for copper conductors, not more than three current-carrying conductors in a raceway or cable, in an ambient temperature of 30 °C. Correction factors apply for higher ambient temperature and for more conductors. Terminations are typically rated lower than the conductor — the lower of the two governs.
Ampacity is limited by how hot the insulation is allowed to get. The same copper conductor carries more current with 90 °C insulation than with 60 °C insulation, because more heat can be tolerated before the insulation degrades.
But the conductor is rarely the weakest link. Common circuit breakers, receptacles and other terminations are usually rated 60 °C or 75 °C, and the code requires the lowest rating in the circuit to be used for the ampacity calculation. A 90 °C conductor on a 75 °C breaker is a 75 °C circuit.
The 90 °C column is used mainly for derating calculations, where the higher starting value leaves more margin after correction factors are applied — not as the circuit's actual ampacity.
Ampacity from the table is a starting point. Several adjustments apply:
References and calculation methods used for this page are listed below. Numbered markers connect table columns where present. A reference listing does not itself establish that every value has been independently checked.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | NFPA 70 National Electrical Code, Table 310.16 — Ampacities of Insulated Conductors | reference | NEC 2023 (NFPA 70-2023) — source |
| Standard | Revision | What it covers on this page |
|---|---|---|
| NFPA 70 National Electrical Code, Table 310.16 | NEC 2023 (NFPA 70-2023) | all ampacity values on this page, for copper conductors at 30 °C ambient |
No page-specific independent source review is recorded here. The listed references and formulas explain the basis of the compilation; automated consistency checks do not verify the original sources or establish product conformity.
These are base ampacities for the stated conditions. Ambient temperature, conductor count, continuous loading and voltage drop all modify the allowable current, and the governing requirement is the adopted code in the jurisdiction of installation.
Read the source notes, calculation methods and verification scope above before reusing a value. To cite this page:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.