Conductor area, diameter and DC resistance for AWG and kcmil cable sizes, with the nearest IEC metric equivalent for substitution.
Data verified 2026-09-29 · based on NEC 2023 edition
| Size[3] | Area mm²[3] | Area kcmil[3] | Conductor diameter mm[1] | DC resistance Ω / 1,000 ft[3] | DC resistance Ω / km[3] | Nearest IEC metric size[2] |
|---|---|---|---|---|---|---|
| 14 AWG # | 2.08 | 4.11 | 1.63 | 3.07 | 10.1 | 1.5 mm² |
| 12 AWG # | 3.31 | 6.53 | 2.05 | 1.93 | 6.34 | 2.5 mm² |
| 10 AWG # | 5.26 | 10.4 | 2.59 | 1.21 | 3.97 | 4 mm² |
| 8 AWG # | 8.37 | 16.5 | 3.26 | 0.764 | 2.51 | 6 mm² |
| 6 AWG # | 13.3 | 26.2 | 4.11 | 0.491 | 1.61 | 10 mm² |
| 4 AWG # | 21.2 | 41.7 | 5.19 | 0.308 | 1.01 | 16 mm² |
| 3 AWG # | 26.7 | 52.6 | 5.83 | 0.245 | 0.804 | 25 mm² |
| 2 AWG # | 33.6 | 66.4 | 6.54 | 0.194 | 0.637 | 25 mm² |
| 1 AWG # | 42.4 | 83.7 | 7.35 | 0.154 | 0.505 | 35 mm² |
| 1/0 AWG # | 53.5 | 106 | 8.25 | 0.122 | 0.400 | 50 mm² |
| 2/0 AWG # | 67.4 | 133 | 9.27 | 0.0967 | 0.317 | 70 mm² |
| 3/0 AWG # | 85.0 | 168 | 10.4 | 0.0766 | 0.251 | 70 mm² |
| 4/0 AWG # | 107 | 212 | 11.7 | 0.0608 | 0.200 | 95 mm² |
| 250 kcmil # | 127 | 250 | 12.7 | 0.0515 | 0.169 | 120 mm² |
| 300 kcmil # | 152 | 300 | 13.9 | 0.0429 | 0.141 | 150 mm² |
| 350 kcmil # | 177 | 350 | 15.0 | 0.0367 | 0.121 | 185 mm² |
| 400 kcmil # | 203 | 400 | 16.1 | 0.0321 | 0.105 | 185 mm² |
| 500 kcmil # | 253 | 500 | 18.0 | 0.0258 | 0.0847 | 240 mm² |
| 600 kcmil # | 304 | 600 | 19.7 | 0.0214 | 0.0703 | 300 mm² |
| 750 kcmil # | 380 | 750 | 22.0 | 0.0171 | 0.0562 | 400 mm² |
Areas, diameters and resistances describe the conductor, not the cable. A finished cable adds insulation, a jacket and often a filler, so its outside diameter is much larger and depends entirely on the insulation type and voltage rating. Resistance values are for uncoated copper at 20 °C; aluminium is about 61% less conductive for the same area, and resistance rises roughly 0.4% per °C above 20 °C. This table deliberately gives no ampacity — current-carrying capacity depends on insulation temperature rating, installation method and ambient temperature, and is covered on the ampacity chart.
The North American system is logarithmic in the small sizes and linear in the large ones, which is why it looks irregular. AWG sizes from 36 down to 0000 are defined so that each three-gauge step doubles the area: 12 AWG to 9 AWG doubles the copper, and 12 AWG to 6 AWG quadruples it. Above 4/0 the system switches to kcmil — thousands of circular mils — and simply counts area: 250 kcmil, 300 kcmil, 500 kcmil and so on.
A circular mil is not a metric unit. It is the area of a circle one thousandth of an inch in diameter, which makes 1 kcmil equal to 0.5067 mm². The unit survives because it makes the arithmetic of wire area trivial: the circular-mil area of a round wire is simply its diameter in mils squared, with no factor of π/4 anywhere.
The IEC system is straightforward metric cross-sectional area — 1.5, 2.5, 4, 6, 10 mm² and the R10 preferred series above that. Because the two series were designed independently, they do not line up: 12 AWG is 3.31 mm² and the nearest IEC size is 2.5 mm², which is 24% less copper. The next IEC size up, 4 mm², is 21% more. Substituting a metric cable for an AWG one always means choosing between an undersized and an oversized conductor, which is why the mapping column shows the nearest size rather than an equivalent.
Voltage drop, power loss and fault-loop impedance are all driven by conductor resistance, not by the size label. Two cables that look similar can differ by 20% in copper cross-section and therefore in resistance.
Three corrections apply to any resistance figure. Temperature: copper's resistivity rises about 0.393% per °C, so a conductor at 75 °C has roughly 22% more resistance than at 20 °C, which is the temperature this table is based on. Material: aluminium has 61% more resistivity than copper for the same cross-section, which is why aluminium cable is always two AWG sizes larger for the same job. Stranding and coating: tinned copper is slightly more resistive than bare, and fine-stranded flexible cable slightly more again, though for power work the difference is small.
For a voltage-drop calculation the whole path counts — out on the live conductor and back on the neutral, so a single-phase circuit has twice the resistance of one conductor length. Three-phase circuits are shorter by a factor of √3 because the return path is shared. That is why a voltage-drop calculator asks for the one-way length and applies the factor itself.
Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | Conductor diameter computed from the cross-sectional area | derived | d = √(4A/π), treating the stranded conductor as a solid round of equivalent area. Real stranded conductors are slightly larger in diameter than the equivalent solid because of the gaps between strands — typically by 2–5% depending on stranding class. |
| [2] | IEC 60228 — Conductors of insulated cables | standard | IEC 60228:2004 |
| [3] | NEC Chapter 9, Table 8 — Conductor properties (uncoated copper, 20 °C) | standard | NFPA 70 National Electrical Code, 2023 edition |
| Standard | Revision | What it covers on this page |
|---|---|---|
| NFPA 70 (NEC) Chapter 9, Table 8 — Conductor properties | NEC 2023 edition | the area and DC resistance columns for uncoated copper at 20 °C |
| IEC 60228 — Conductors of insulated cables | IEC 60228:2004 | the metric conductor cross-sectional areas in the mapping column |
| ASTM B258 — Standard nominal diameters and cross-sectional areas of AWG conductors | ASTM B258-18 | the AWG size definitions themselves |
Cross-checked against:
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| Conductor diameter | d = √(4A/π) from the metric area. Checked at build time against every row to within 2%. Stranded conductors are 2–5% larger in diameter than the equivalent solid. |
Dimensions and resistances are for the bare copper conductor at 20 °C. Outside diameter depends on insulation and voltage rating and is not given here. Resistance rises about 0.393% per °C, so a conductor at its 75 °C rating has roughly 22% more resistance than the table shows. Ampacity is intentionally excluded — see the ampacity chart for current ratings with their installation basis stated.
Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.