Engineering Reference

Wire Gauge (AWG) Chart

American Wire Gauge to diameter, cross-sectional area and DC resistance — AWG 0000 through 40, in metric and imperial units, with a searchable table and a cross-section converter.

Data verified 2026-09-29 · based on ASTM B258-18

Quick Answer

AWG is a reverse logarithmic scale: a larger gauge number means a thinner wire. Decreasing the AWG number by 10 multiplies the cross-sectional area — and therefore the current capacity — by roughly 10. AWG 10 is about 5.26 mm² and AWG 20 is about 0.52 mm².

American Wire Gauge (AWG) Table

AWG[1]Diameter
in[1]
Diameter
mm[2]
Area
kcmil[1]
Area
mm²[2]
Resistance
mΩ/m[3]
Resistance
mΩ/ft[3]
0000 (4/0) #0.4611.6842121070.16080.04901
000 (3/0) #0.409610.40516885.00.20280.06180
00 (2/0) #0.36489.26613367.40.25570.07793
0 (1/0) #0.32498.25110653.50.32240.09827
1 #0.28937.34883.742.40.40660.1239
2 #0.25766.54466.433.60.51270.1563
3 #0.22945.82752.626.70.64650.1970
4 #0.20435.18941.721.20.81520.2485
5 #0.18194.62133.116.81.0280.3133
6 #0.1624.11526.313.31.2960.3951
7 #0.14433.66520.810.51.6340.4982
8 #0.12853.26416.58.372.0610.6282
9 #0.11442.90613.16.632.5990.7921
10 #0.10192.58810.45.263.2770.9989
11 #0.09072.3058.234.174.1321.260
12 #0.08082.0536.533.315.2111.588
13 #0.0721.8285.182.626.5712.003
14 #0.06411.6284.112.088.2862.525
15 #0.05711.453.261.6510.453.184
16 #0.05081.2912.581.3113.174.016
17 #0.04531.152.051.0416.615.064
18 #0.04031.0241.620.82320.956.385
19 #0.03590.9121.290.65326.428.051
20 #0.0320.8121.020.51833.3110.15
21 #0.02850.7230.8100.41042.0012.80
22 #0.02530.6440.6420.32652.9616.14
23 #0.02260.5730.5090.25866.7920.36
24 #0.02010.5110.4040.20584.2225.67
25 #0.01790.4550.3200.162106.232.37
26 #0.01590.4050.2540.129133.940.81
27 #0.01420.3610.2020.102168.951.47
28 #0.01260.3210.1600.0810212.964.90
29 #0.01130.2860.1270.0642268.581.84
30 #0.010.2550.1010.0509338.6103.2
31 #0.00890.2270.07970.0404426.9130.1
32 #0.0080.2020.06320.0320538.3164.1
33 #0.00710.180.05010.0254678.8206.9
34 #0.00630.160.03980.0201856.0260.9
35 #0.00560.1430.03150.01601079329.0
36 #0.0050.1270.02500.01271361414.8
37 #0.00440.1130.01980.01001716523.1
38 #0.0040.1010.01570.007972164659.6
39 #0.00350.08970.01250.006322729831.8
40 #0.00310.07990.009890.0050134411049

Diameter and area are for solid copper conductors. Resistance is DC at 20 °C. Values are given to the precision published in the source standard; small rounding differences of up to about 2% may appear between the inch and millimetre columns.

Cross-Section (mm²) to Nearest AWG

How the AWG Scale Works

AWG is defined so that two consecutive gauges differ in diameter by a fixed ratio. The scale is inverse — the number increases as the wire gets thinner — and it runs from 0000 (written 4/0) at the thick end to 40 and beyond at the thin end.

The defining relationship for gauge n is:

diameter (inch) = 0.005 × 92(36 − n)/39

The practical consequence of the ratio 921/39 ≈ 1.1229 is that a change of ten gauge numbers changes the area by about ten times. That is why a 10 AWG wire carries roughly ten times the current of a 20 AWG wire.

AWG vs mm² — Why Both Are Used

North American practice sizes conductors by AWG; most of the rest of the world sizes them by cross-sectional area in mm². The two systems do not convert exactly, because AWG defines a diameter while mm² defines an area. Common approximate equivalents:

Choosing a Wire Gauge

Gauge selection is driven by three constraints, and the binding one is usually temperature rise rather than voltage drop:

The resistance values in the table let you calculate voltage drop directly: Vdrop = 2 × length × current × resistance per unit length for a single-phase two-wire circuit.

Frequently Asked Questions

Is a higher AWG number thicker or thinner?
Thinner. AWG is a reverse scale — the number increases as the wire gets thinner. AWG 10 is thicker than AWG 20.
What is AWG 10 in mm²?
AWG 10 has a nominal cross-sectional area of 5.26 mm² and a diameter of 2.588 mm (0.1019 in).
How much does gauge change current capacity?
Roughly tenfold per ten gauge numbers, because the cross-sectional area changes by about a factor of ten. AWG 10 carries roughly ten times the current of AWG 20 under the same conditions.
What does 2/0 or 4/0 mean?
Gauges larger than 0 are written as fractions — 2/0 (also 00) and 4/0 (also 0000). These are thicker than AWG 0, with 4/0 the thickest in common use at 11.684 mm diameter and 107 mm².
Does AWG apply to stranded wire?
Yes. A stranded conductor is specified by its total equivalent AWG, which refers to the total copper cross-section. The overall diameter is larger than the equivalent solid gauge because of the air gaps and the stranding lay.
Why is resistance listed per metre and per foot?
North American work is usually calculated in feet and metric work in metres. Both are given so voltage-drop calculations can be done in either system without conversion.

Related

Value Sources

Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.

#SourceTypeRevision / method
[1]ASTM B258 — Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG SizesstandardASTM B258-18 — source
[2]Millimetre and area conversionderivedInch values × 25.4. Area in mm² computed as π/4 × d², then rounded to 3 significant figures as published.
[3]Copper DC resistance at 20 °Cderivedρ = 1.7241 × 10⁻⁸ Ω·m (IACS annealed copper) applied to the nominal cross-sectional area from ASTM B258. Does not include stranding factor.

Data Sources

StandardRevisionWhat it covers on this page
ASTM B258 — Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG SizesASTM B258-18nominal conductor diameter and cross-sectional area for each AWG size

Cross-checked against:

Nominal values as published in the referenced standard. Manufacturing tolerances apply.

Accuracy and use. The values on this page are compiled from the published standards and cross-checked sources listed above. Where values are derived, the derivation is stated. No warranty, express or implied, is made as to the accuracy or completeness of this information, and no liability is accepted for any loss or damage arising from its use. Engineering reference data is provided for guidance in preliminary work — before a value is used for design, fabrication or acceptance testing, verify it against the current revision of the governing standard and against your own inspection. The user assumes all risk and responsibility in connection with the use of this information.

Cite This Page

Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:

Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.