R-value per inch of thickness for 29 insulation materials and building products, from aerogel at R-10 per inch down to concrete at R-0.08.
Data verified 2026-09-29 · based on ASHRAE Handbook, 2021 Fundamentals volume
| Material[1] | Class[1] | R per inch h·ft²·°F/BTU·in[1] | RSI per 25 mm K·m²/W[3] | RSI per m K·m²/W[3] | Density kg/m³[1] | Note[1] |
|---|---|---|---|---|---|---|
| Aerogel blanket # | High performance | 10.00 | 1.733 | 69.335 | 140 | Highest R per inch available; costly and dusty to install |
| Polyurethane board (closed cell) # | Rigid foam | 6.00 | 1.04 | 41.601 | 32 | Highest of the common rigid foams |
| Polyisocyanurate board # | Rigid foam | 5.70 | 0.988 | 39.521 | 30 | Slightly lower than polyurethane; common in roofing |
| Closed-cell spray foam # | Spray foam | 6.50 | 1.127 | 45.068 | 32 | Also acts as an air barrier and can add structural stiffness |
| Extruded polystyrene (XPS) # | Rigid foam | 5.00 | 0.8667 | 34.668 | 35 | Moisture resistant; the standard below-grade board |
| Expanded polystyrene (EPS) # | Rigid foam | 3.85 | 0.6673 | 26.694 | 20 | Cheaper than XPS and nearly as good when dry |
| Open-cell spray foam # | Spray foam | 3.60 | 0.624 | 24.961 | 8 | Air barrier but not a vapour barrier; lower R per inch |
| Phenolic foam board # | Rigid foam | 7.00 | 1.213 | 48.535 | 35 | High R per inch with good fire performance |
| Mineral wool batt # | Fibrous batt | 3.30 | 0.572 | 22.881 | 40 | Non-combustible; better than glass at high temperature |
| Fibreglass batt (standard) # | Fibrous batt | 3.14 | 0.5443 | 21.771 | 10 | The baseline batt; R-13 for a 3.5 in wall cavity |
| Fibreglass batt (high density) # | Fibrous batt | 3.80 | 0.6587 | 26.347 | 20 | Fits the same cavity with higher R |
| Cellulose loose fill # | Loose fill | 3.60 | 0.624 | 24.961 | 40 | Recycled paper with fire retardant; must be installed at the right density |
| Mineral wool loose fill # | Loose fill | 3.00 | 0.52 | 20.8 | 40 | Blown mineral wool; non-combustible |
| Fibreglass loose fill # | Loose fill | 2.50 | 0.4333 | 17.334 | 10 | Settles over time; install above the nominal thickness to compensate |
| Vermiculite loose fill # | Loose fill | 2.20 | 0.3813 | 15.254 | 100 | Largely historical; may contain asbestos in pre-1990 installations |
| Perlite loose fill # | Loose fill | 2.70 | 0.468 | 18.72 | 100 | Lightweight mineral fill |
| Wood fibreboard # | Structural board | 3.50 | 0.6067 | 24.267 | 250 | Can serve as sheathing and insulation together |
| Cork board # | Structural board | 3.60 | 0.624 | 24.961 | 120 | Renewable, dimensionally stable |
| Cotton batt (recycled denim) # | Fibrous batt | 3.70 | 0.6413 | 25.654 | 25 | Similar performance to fibreglass; requires careful fire treatment |
| Sheep wool batt # | Fibrous batt | 3.60 | 0.624 | 24.961 | 25 | Moisture buffering; higher cost |
| Vacuum insulation panel # | High performance | 25.00 | 4.333 | 173.34 | 200 | Highest R per inch by far, but loses most of it if punctured |
| Softwood lumber # | Structural | 1.25 | 0.2167 | 8.6669 | 500 | Timber is a poor insulator but a structural necessity |
| Plywood and OSB # | Structural | 1.25 | 0.2167 | 8.6669 | 600 | Similar to solid wood |
| Gypsum board # | Structural | 0.90 | 0.156 | 6.2402 | 800 | Half-inch board is about R-0.45 total |
| Brick # | Masonry | 0.20 | 0.03467 | 1.3867 | 1900 | Poor insulator; adds thermal mass rather than resistance |
| Concrete (normal weight) # | Masonry | 0.08 | 0.01387 | 0.55468 | 2400 | Very poor per inch — an 8 in wall is only about R-0.6 |
| Concrete block (hollow) # | Masonry | 1.10 | 0.1907 | 7.6269 | 1200 | Empty cores help; filled or grouted block is closer to solid concrete |
| Stone # | Masonry | 0.08 | 0.01387 | 0.55468 | 2700 | Similar to concrete |
| Glass (single pane) # | Glazing | 0.02 | 0.003467 | 0.13867 | 2500 | Essentially no insulating value; the air film does the work |
R-value is a per-inch figure here, and total R is that number times the thickness. A material's rated R-value only applies at its stated thickness and installed density — loose fill installed below its rated density performs worse than the bag claims, and batts compressed into a cavity lose R in proportion to how much they are squeezed.
Two things this table does not capture. The first is air movement: fibrous insulation works by trapping air, so any convection loop inside it or air washing through it destroys a large part of its value — which is why an air barrier and a wind barrier matter as much as the R-value. The second is thermal bridging: studs, joists and slab edges conduct heat around the insulation, so an assembly's effective R is always lower than the insulation's nominal R.
R-value also falls with moisture and, for foams, with the ageing of the blowing agent. Polyisocyanurate in particular loses some of its rated R over the first few years as the low-conductivity gas escapes, which is why long-term values are quoted separately from initial ones.
Three quantities describe the same physics in different units, and mixing them up is the usual error.
R-value is thermal resistance in imperial units, in h·ft²·°F/BTU. R-values add: a wall with R-13 insulation, R-0.5 sheathing and R-0.45 drywall has a total of about R-14 plus the surface films, before bridging is considered.
RSI is the same quantity in SI units, in K·m²/W. The conversion is 1 R = 0.176110 RSI, so R-13 is RSI 2.29. Because R is per inch and RSI is per metre of thickness in some tables and per 25 mm in others, always check which basis a metric figure uses.
U-factor is the reciprocal of total R, in BTU/h·ft²·°F. It describes how much heat flows, so lower is better — the opposite direction to R. A wall of total R-20 has a U of 0.05. U is what appears in heating and cooling load calculations, and it is what window ratings quote, because glazing is rated on heat flow rather than on resistance.
Keep them straight by remembering which direction is good: higher R is better, lower U is better.
The R-value on an insulation bag is measured on the insulation alone, in a laboratory, dry and undisturbed. An assembly in a real wall performs measurably worse, for three reasons that compound.
Thermal bridging. Studs at 16 in on centre occupy about 25% of a 2×4 wall's area and have an R-value of roughly 1.25 per inch against the insulation's 3.14. The framing short-circuits the insulation, and a nominal R-13 wall performs closer to R-11. Continuous exterior insulation, or advanced framing with studs at 24 in on centre, addresses this directly.
Air leakage. Fibrous insulation does nothing to stop air moving through it. A leaky wall loses far more heat to air exchange than to conduction through the insulation, which is why air sealing is usually the highest-return first step — and why it should come before adding more insulation.
Moisture. Wet insulation conducts much better than dry, and most fibrous materials lose a large fraction of their R when saturated. The design response is not more insulation but a correct vapour and drainage strategy, so the assembly dries rather than accumulates.
The practical order is: air seal first, then address bridging, then add insulation. Adding R to a leaky, bridged assembly delivers much less than the arithmetic suggests.
Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | ASHRAE Handbook — Fundamentals, thermal insulation and building envelope chapters | standard | ASHRAE Handbook, 2021 Fundamentals volume |
| [2] | ASTM C518 — Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus | standard | ASTM C518-21 |
| [3] | Value computed from the standard's defining relationship | derived | Computed at build time from the defining formula and verified against every row. |
| Standard | Revision | What it covers on this page |
|---|---|---|
| ASHRAE Handbook — Fundamentals, thermal insulation and envelope chapters | ASHRAE Handbook, 2021 Fundamentals volume | the R-values per inch of thickness |
| ASTM C518 — Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus | ASTM C518-21 | the method behind the measured R-values |
| ASTM C168 — Standard Terminology Relating to Thermal Insulation | ASTM C168-19 | the definitions of R-value, RSI and U-factor |
Cross-checked against:
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| RSI per 25 mm and RSI per metre | RSI = R × 0.176110, the exact conversion. The per-metre column is the per-25 mm column multiplied by 40. Both are recomputed at build time; the two bases are given separately because metric tables use each. |
R-values are per inch of thickness for the material alone, dry and undisturbed. Installed performance is lower: loose fill installed below rated density underperforms, compressed batts lose R proportionally, foam loses some R as the blowing agent ages, and any assembly loses more to thermal bridging and air leakage. Total assembly R is not the sum of the insulation R-values.
Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.